EasyManua.ls Logo

Bosch AMC-4W - Connecting Relay Outputs

Bosch AMC-4W
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing the AMC-4W Access Controller AMC-4W
36 Installation Guide Bosch Security Systems | V.3.1/2006-09
5.11. Connecting Relay Outputs
To operate locks or alarm systems the AMC-4W has eight form C relay
outputs.. Each relay output can operate in ‘wet’ mode, using the AMC-4W's
internal 12V DC power supply for external devices or ‘dry’ mode with potential
free contacts for externally powered systems.
Figure 24: Wet mode and dry mode of the AMC-4W relay outputs
Maximum switching power of each relay output using resistive load is 60 VA,
maximum switching voltage 30 V DC and maximum switching current 1,25 A.
If there is inductive load diodes should be installed across the DC load. Diodes
(BAX12A) are supplied with every AMC-4W package.

Table of Contents