FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
In overview | en 15
Bosch Sicherheitssysteme GmbH User Guide 2020-07 | 3.0 | F.01U.378.877
Y General disabled
Y General fault
Y** Fire detector fault / disabled
Y** Signaling device fault / disabled
Y** Alarm transmission device fault / disabled
Y** Output to fire protection equipment fault / disabled
Y Power fault
G Power available
Y System/panel fault
G System in operation
R Programmable LED for a self-defined alarm
Y** Programmable LED for a self-defined fault/diasablement
*Y=yellow, R=red, G=green
**blinking: fault, steady: disabled
The LEDs for the status of devices like detectors , signaling devices , alarm
transmission devices and the outputs to fire protection equipment always light up in
combination with the general fault or general disabled icon according to their
status. Additionally, in case of a fault the LED of the respective element is blinking while the
LED indicating the general fault lights up steadily yellow.