84 en | Further functions
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
Fire alarm Fault/ supervisory alarm
Display switches to Alarm indication Fault indication
Fire drill after event ends Must be restarted
manually
Continue
A new function cannot be selected until the fault/supervisory alarm and/or the fire drill have
been completed.
19.7 Alarm Counters
Show Lifetime Event Counters
During the lifetime of the panel, the following alarm conditions and messages are counted
locally for each panel (Local) and in scope for all panels within the complete network or a
network group, depending on the configuration (Scope):
External alarm: all fire alarm conditions which triggered an external device
Internal alarm: all fire alarm conditions which did not trigger an external device (e.g. if the
alarm occurred in daymode)
Maintenance alarm: all alarm messages from detectors in walktest mode.
To display the number of alarm conditions and messages which have been counted so far:
1. In the start menu, select Further functions
2. Alarm counters
The figure after the message type shows the number of conditions and messages counted so
far for the individual panel (Local) and summed up for all panels in the complete network or a
network group, depending on the configuration (Scope).
Notice!
The scope of the counters depends on the configuration of Scope of the node in the
FSP-5000-RPS programming software. If Group is set, conditions and alarms of all panels
within a particular network group, depending on the logical node address, are counted. If
Network is set, all conditions and alarms of all panels within the complete network are
counted.
Reset counters
You can reset the alarm counter for individual alarm types to 0.
To reset alarm counters
1. In the start menu, select Further functions
2. Alarm counters
3. Mark the alarm counter you require (e.g. external alarm)
4. Select Reset
5. Confirm the message "Attention: Counter will be reset" with OK to reset the alarm
counter to 0 or select Cancel to cancel the operation.
6. Reboot the panel to display the reset values.
Notice!
In order to reset alarm counters, you need authorization level 4.