FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Further functions | en 83
Bosch Sicherheitssysteme GmbH User Guide 2020-07 | 3.0 | F.01U.378.877
The transmission of messages to the Remote Portal is stopped until the next restart of
the panel controller.
– To unblock the service select Unblock Remote Alert.
Notice!
The Blocking/Unblocking of Remote Alert is done for all panels in the network. You cannot
block/unblock this service for a single panel.
19.5 Change password
Notice!
If all operators with the same access authorization have the same password, this function
cannot be used.
1. In the start menu, select Further functions
2. Change password
A list of all operators is displayed.
3. Select the list field you require.
4. Enter the password.
On the display, each digit of the password is indicated with an asterisk so that nobody
else can see the password.
5. Enter a new password and repeat the entry in the bottom field again.
6. Select OK to confirm the entry or Cancel to cancel the operation.
19.6 Performing a fire drill
During a drill, all signaling devices are activated.
Caution!
If a genuine alarm is reported during a fire drill, the fire drill is abandoned. The fire drill can
only be restarted when the alarm is ended.
To start a drill:
1. In the start menu, select Further functions
2. Drill
3. Confirm Start drill with OK
The drill is started.
To end the drill, select Stop drill.
During the fire drill, fire alarms, fault messages and supervisory alarms are displayed.
To switch between the fire drill display and the message display in question, select Return to
message screen or Return to drill screen on the status bar.
If an alarm or a fault/supervisory alarm is sounded during a fire drill, the panel controller
reacts as described in the table below:
Fire alarm Fault/ supervisory alarm
The drill signaling devices are
switched off.
Yes No
The drill is automatically
terminated.
Yes No