54 en | Block
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
12 Block
This chapter contains information about the following points:
–
Blocking and unblocking elements, page 54
–
Displaying list of all blocked elements, page 54
Caution!
All alarm and fault messages from blocked detectors are no longer displayed.
12.1 Menu overview
Bypass
Block
-> Bypass Show blocked devices Select by
number
Block Group Printer
Block -> Sounder Strobe HVAC Doorholder
Transmission device Detector Extinguishing
system
Annunciator
Logical zone More... -> Control
element
Interface
module
12.2 Blocking and unblocking elements
Select the element you require in the submenu.
Example:
To block a detector, select the following in the start menu:
1. Bypass Block
2. Block
3. Detector
Various selection criteria are displayed. See also
Working with lists, page 24
.
4. Select a selection criterion, e.g. By description.
A list of the detectors is displayed. Refer to
Scrolling through lists, page 25
for
information on how to scroll forward and backward through the list.
5. Select the required list fields.
The list fields are marked.
6. Select Block.
The selected elements are blocked.
To unblock the elements again, repeat all previous steps but select Un- block in step 6.
C
A C after a detector means that this detector is part of a closed group and cannot be blocked
individually. In order to block a detector marked in this way, please select Logical zone in step
3.
12.3 Displaying list of all blocked elements
12.3.1 Using the menu
To display a list of all blocked elements, select the following in the start menu:
1. Bypass Block
2. Block