18 en | In overview
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
Text Meaning
Panel 4-1 Logical node address
Level 3 logged in Access level of the operator who is logged in.
Possible levels: 2, 3 or 4
Only displayed in the main menu.
Bypass Block\Block\Detector Menu path of the selected menu
For reasons of space it is not always possible to display the
complete path.
Menu field
To select a main menu, touch the corresponding menu field on the touch screen. In
All
functions at a glance, page 11
, there is an overview of all main menus with their respective
submenus.
Status bar
0
Fire
0
Control
8
Fault
0
Bypass Status
This status bar is available on each menu. In addition, other status bars are offered in some
menus; see also
Switching between status bars, page 29
:
The leading number specifies the number of elements in the respective state:
Fire Number of groups that have triggered a fire alarm
Control Elements that are activated
Fault Elements that have reported a fault
Bypass Disabled elements
In addition it is possible to display an overview of the type and nature of all message types
received by the panel:
Status Display of a list of the various message and status types and the
number of elements in the respective state
To display the individual elements, touch the relevant field with your finger.
The Control and Fault status fields are identified by the letters "B" and/or "C":
"B" means that controllers for type B fire protection equipment (G-B) are affected (e.g.
control elements without acknowledgement).
"C" means that controllers for type C fire protection equipment (G-C) are affected (e.g.
extinguishing systems).
4.4 Standby screen
When the touchscreen is not operated, its backlight switches off after 5 minutes.
Notice!
In case of an active alarm or fault message, the backlight switches off after 60 minutes. The
display switches back to this message from any other element of the menu after 30 seconds.
If the screen is black, touch it gently to display the standby screen. The following information
is displayed on the standby screen:
Date