58 en | Diagnostics
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877 User Guide Bosch Sicherheitssysteme GmbH
3. Select Display test.
First the buzzer is switched on for a short time. Then the display is filled with the colors
black, white, red, green and blue. After this, line by line, the display turns to these colors
from the top to the bottom and then changes again to the Hardware menu.
13.4.2 CAN-Bus
Select CAN bus to display the status of the CAN interfaces.
13.5 Panel Passport
Select Panel passport to display the following diagnostic information:
– License model of the panel controller (premium or standard)
– CAN ID
– Production date
– BOM revision
– PCBA material number
– Material number
– Software version
– Build type
– Build number
– Serial number
– MAC Address
13.6 LED Test on modules
To test the LED display of selected modules:
1. In the start menu, select Diagnostics
2. LED test on modules
A list of various selection criteria is offered:
– Select LED test all modules to test the LED display of all modules.
– Select By number or By type to test the LED display of individual selected modules.
Example
To test the LED displays of an LSN 300 module:
1. Select By type.
A list of all module types is displayed.
2. Select the LSN 300 module.
A list of all LSN 300 modules is displayed.
3. Select the list field(s) you require. The list fields are marked.
4. Select Activate LEDs.
The LEDs are activated for the duration of approx. five seconds.
Notice!
The numbers before the module names indicate the slot of the module on the panel.
13.7 Network services
13.7.1 Routing table
To display routing information:
1. In the start menu, select Diagnostics
2. Network services