152/176 Start-up and parameterization
Bosch Rexroth AG, MIT: ID 40, 3 842 530 344/2014-05
11 Start-up and parameterization
11.1 Starting up Profibus DP
Every SLK comes from the factory with the node number 126 preset.
To operate the SLK on a production line, only this node number has to be changed
according to the existing Profibus topology.
There are two ways to do this:
• Configuration and diagnostics software
• With the Profibus DP master
One easy way to label the SLK is to write the configured node number on the
provided area of the SLK nameplate with a dry erase marker.
If the node number is later changed, the label also has to be changed to avoid
misinterpretation.
The PDP node number is briefly displayed after turning on the SLK.
Example: A node number of 4 is configured:
Fig. 32: Display of configured node number
11.1.1 Configuring through the web interface
The “Fieldbus Settings” link on the ID 40/SLK homepage allows the PDP node
number to be read and configured, see Chapter 10.5.6 “Fieldbus settings page”.
The new node number is only applied by the system when the SLK is temporarily
offline on the fieldbus. The fieldbus indicators cannot appear on the SLK display
(see Chapter 2.2.2 “Status display”).
Fig. 33: The fieldbus activity indicator on the display is off