EasyManua.ls Logo

Bosch Rexroth IndraControl L40 - Digital Onboard Inputs; Fig. 7-12: Digital Inputs

Bosch Rexroth IndraControl L40
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-8 Connections and Interfaces IndraControl L40
DOK-CONTRL-IC*L40*****-PR02-EN-P
Digital Onboard Inputs
The left-hand section of the plug panel provides eight digital inputs as
onboard inputs.
Slots 1 and 2:
Eingänge.FH9
Fig. 7-12: Digital inputs
Note: Observe the color-coding of the connectors.
Number of inputs 8
Connection method 2-wire connection
Electric isolation from U
S
No
Electric isolation from U
L
Yes
Reverse voltage protection Yes
Input voltage:
Nominal value at "0"
Nominal value at "1"
3 V ... + 5 V
11 V ... 30 V
Input current:
Nominal value at "0"
Nominal value at "1"
< 2.5 mA
2.8 mA ... 6 mA
Delay time:
If "0" to "1"
If "1" to "0"
Typ. 50
µ
s
Typ. 50
µ
s
Current consumption by 24-V supply (U
S
) Typ. 60 mA
Cable length (unshielded) < 100 m
Interrupt inputs 8
Sensor supply From U
S
via a PTC fuse
Output voltage Typ. Uext. 1V
Nominal current (total) 0.2 A
Short-circuit protection, overcurrent protection Typ. 0.6 A
IAS COMPONENTS www.ias-components.com info@ias-components.com