7-10 Connections and Interfaces IndraControl L40
DOK-CONTRL-IC*L40*****-PR02-EN-P
Number of outputs 8
Connection method 2-wire connection
Type of outputs
• Semi-conductor outputs,
non-latching
• Protected, with automatic
restart
• Current-carrying
Electric isolation from U
S
No
Electric isolation from U
L
Yes
Output voltage, nominal value 24 V
Rated output current
Nominal value
Maximum value according to DIN EN 61131-2
1-signal
0-signal (leakage current)
0.5 A
≤ 0.6 A
2 mA ... 0.6 A
≤ 0.5 mA
Maximum total current of outputs 2 A
Parallel connection of outputs Yes, but only within one
terminal
Output delay time < 500
µ
s
Contactor size (at 1 Hz) SG1 (6.2 W)
Lamp load (at 8 Hz) 5 W
Switching frequency
• With ohmic load
• With inductive load
100 Hz
Function (contactor)
Overload protection:
• Typical current level, causing switchoff
• Minimum current level, causing switchoff
• Automatic restart with reduced load
1.2 A
0.6 A
After approx. 10 msec
Overload indicator Red collective LED for all 8
outputs
Voltage reduced on circuit interruption in the
nominal operating mode, limited to
Electronically to (Vext – 50 V)
Typ. 26 V
Reverse voltage protection Ensured without connected
load
Supply voltage according to EN 61131-2 24 V DC
Open-circuit power consumption from U
S
Typ. 50 mA
Cable length (unshielded) < 100 m
Fig. 7-16: Data of digital outputs
Light-emitting diodes indicating the current state of the outputs are
arranged above the output terminals.
LEDs 1, 2, 3, 4 Meaning
Off The assigned output is not set.
Yellow The assigned output is set.
Fig. 7-33: Status LEDs of digital outputs