EasyManua.ls Logo

Bosch Rexroth IndraControl L40 - Indicators on the Input;Output Modules

Bosch Rexroth IndraControl L40
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-16 Structure of the Rexroth Inline Terminals IndraControl L40
DOK-CONTRL-IC*L40*****-PR02-EN-P
Indicators on the Input/Output Modules
12
11
12
11
12
11
12
11
12
11
1
2
D
1
2
D
1
3
2
4
1
2
1
2
1
2
1
2
Modulanzeige.FH9
Fig. 9-28: Indicators on the input/output modules
The following states are indicated by the input/output modules:
LED Color State Description of LED states
On Local bus active
Flashing:
0.5 Hz
(slow)
Logic voltage available, local bus not active
2 Hz
(medium)
Logic voltage available, local bus active,
peripheral failure pending
4 Hz
(fast)
Logic voltage available; module upstream of
the flashing module failed; or module itself is
defective.
Modules downstream of the flashing module
are not included in the configuration scope.
D
(1)
Green
Off Logic voltage not available; local bus not active
Fig. 9-29: Diagnostic LED of input/output modules
The state of the input or output is indicated by the corresponding yellow
LED:
LED Color State Description of LED states
On The assigned input/output is set.
1, 2, 3,
4
(2)
Yellow
Off The assigned input/output is not set.
Fig. 9-33: Status LEDs of input/output terminals
Assignment between status LED and input/output
Please refer to the functional description for information on the
assignment of a status LED to the corresponding input/output.
Diagnosis
Status
IAS COMPONENTS www.ias-components.com info@ias-components.com

Table of Contents

Related product manuals