7-12 Connections and Interfaces IndraControl L40
DOK-CONTRL-IC*L40*****-PR02-EN-P
The interface is electrically isolated. A maximum potential difference of
2 V must be ensured by an appropriate potential equalization between the
control and the remote station.
After power on, the following default parameters are set in the
IndraControl L40:
9600 bauds
No parity
8 data bits
1 stop bit
These parameters can be changed via the software or by the application
program.
Ethernet Interface
Connector X7E can be used to connect the IndraControl L40 to an
Ethernet network.
The connection requirements defined for 100BaseT in IEEE 802.3 are
applicable to Ethernet network connections.
RJ45 female connector, 8-pin
Type: Ethernet 100BaseT
Cable length: Max. 100 m
Cable type: Shielded twisted pair
Transmission rate: 10 or 100 Mbits/s
Max. 100 m
1
8
2
1
3
4
5
6
7
8
Ethernet RJ45
To the network
Ethernet
Ethernet_sst.cdr
Fig. 7-19: Ethernet interface
Bosch Rexroth recommend the use of an STP cable of category 5.
X7E
Ethernet Network Connection