IndraControl L40 Installation and Maintenance 8-15
DOK-CONTRL-IC*L40*****-PR02-EN-P
Connecting the Analog Output Module R-IB IL AO ...
Note:
Connect the shield system via the shield connector (see
page 8-17, "Connecting Shielded Lines Via the Shield
Connector").
Connect the shield system to the FE potential over as large
an area as possible.
Note: Development of ground loops!
The shielding system may be connected directly to the
ground potential at one point only.
If lines are more than 10 meters in length, they should
always be decoupled by means of an RC element (on the
actuator side).
The typical value of the capacitor C should range from 1 nF to
15 nF. The value of the resistor R should be at least 10 M.
A
B
RC
Aktoranschluss.FH9
L: A Module side
B Actuator side
Fig. 8-11: Connection of actuators, in case of signal lines > 10 m