Format Description
CCC Point ID Number or User Number (comprised of three hex digits), 000 means
no point or user information
S Checksum digit
Table 11.5: Contact ID Format Breakdown
SIA Format
SIA is a special format of using frequency shift keying (FSK) rather than a pulse to
communicate quickly.
SIA format is # AAAAAA N GGGGGG EE CCCCCC.
Format Description
# Begin of Subscriber ID Number
AAAAAA Subscriber ID Number
N Begin of event
GGGGGG Group / Area Number , User Number or Codepad Number
EE Event Code
CCCCCC Event Qualifier
Table 11.6: SIA Format Breakdown
System Reporting List
Index Event Description CID
Event
Code
CID Point ID SIA
Event
Code
String (Email / Codepad Display)
1 ZoneAlarm 1130 Zone 1 - 8 / 16 BA Z$$ Alarm
2 ZoneAlarmRestore 3130 Zone 1 - 8 / 16 BH Z$$ Alarm Restore
3 ZoneTrouble 1380 Zone 1 - 8 / 16 BT Z$$ Trouble
4 ZoneTroubleRestore 3380 Zone 1 - 8 / 16 BJ Z$$ Trouble Restore
5 ZoneBypass 1573 Zone 1 - 8 / 16 BB Z$$ Bypass
6 ZoneUnBypass 3573 Zone 1 - 8 / 16 BU Z$$ UnBypass
7 24HrZoneAlarm 1133 Zone 1 - 8 / 16 BA 24Hr Z$$ Alarm
8 24HrZoneAlarmRestore 3133 Zone 1 - 8 / 16 BH 24Hr Z$$ Alarm Restore
9 24HrFireZoneAlarm 1110 Zone 1 - 8 / 16 FA 24Hr Fire Z$$ Alarm
10 24HrFireZoneAlarmRestore 3110 Zone 1 - 8 / 16 FH 24Hr Fire Z$$ Alarm Restore
11 24HrMedicalZoneAlarm 1100 Zone 1 - 8 / 16 MA 24Hr Medical Z$$ Alarm
12 24HrMedicalZoneAlarmRestor
e
3100 Zone 1 - 8 / 16 MH 24Hr Medical Z$$ Alarm Restore
13 24HrPanicZoneAlarm 1120 Zone 1 - 8 / 16 PA 24Hr Panic Z$$ Alarm
11.22.2
11.22.3
82 en | Communication Information Control Panel