If Simultaneous Heat/Cool is turned OFF, Auto changeover time:
Adjustable from 5 to 120 minutes. Default = 30 minutes
NOTE: AUTO mode is intended to switch between Heating and Cooling
modes based on temperature demand. A gradual auto transition is the
energy-conscious default that will satisfy the majority of customers.
Some customers might have significant and simultaneous heating and
cooling demands in different zones. To address this need, a special
simultaneous heating and cooling demand auto mode could be enabled
by the Installer. The simultaneous heating and cooling demand auto
mode will result in higher energy usage but benefit the customer with
greater comfort.
A160183_2
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes
between Fahrenheit (°F) and Celsius (°C). Ex: A 2° deadband will be 2°F
or 2°C and does not change with units, °F and °C. This can allow one
setting to “push” the other to maintain this difference. When the correct
deadband is set, touch SAVE.
Deadband: Adjustable from 0 to 6°. Default = 2°

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant Evolution Connex Control SYSTXBBECC01-C and is the answer not in the manual?

Bryant Evolution Connex Control SYSTXBBECC01-C Specifications

General IconGeneral
BrandBryant
ModelEvolution Connex Control SYSTXBBECC01-C
CategoryThermostat
LanguageEnglish

Related product manuals