Electrical installation
11 ELECTRICAL INSTALLATION
Thereare2connectionoptionsfortype8692/8693:
Multi-polewithcircularplug-inconnector
Cableglandwithconnectionterminals
Signal values
Operatingvoltage: 24VDC
Set-pointvalue
(process/positioncontroller): 0...20mA;4...20mA
0...5V;0...10V
Actualvalue
(onlyprocesscontroller): 4...20mA;
frequency;
Pt 100
11.1 Safety instructions
DANGER
Risk of injury due to electrical shock.
Beforereachingintothesystem,switchothepowersupply
andsecuretopreventreactivation.
Observeapplicableaccidentpreventionandsafetyregula-
tionsforelectricalequipment.
WARNING
Risk of injury from improper installation.
Installationmaybecarriedoutbyauthorizedtechnicians
onlyandwiththeappropriatetools.
Risk of injury from unintentional activation of the system and
uncontrolled restart.
Securesystemagainstunintentionalactivation.
Followinginstallation,ensureacontrolledrestart.
Using the 4...20 mA set-point value input
Ifseveraldevicesoftype8692,8693areconnectedin
seriesandthepowersupplytoadeviceinthisseries
connectionfails,theinputofthefaileddevicebecomes
highlyresistive.Asaresult,the4...20mAstandardsignal
fails.InthiscasepleasecontactBürkertServicedirectly.