45
2023/03 - Revision index: A - Code: 0000139233
17. Default parameters
Langue = English
Setpoints = 7.4 pH; 700 mV; 1.2 ppm
Dosing method = Acid (pH); Low (ORP)
OFA Time = OFF
Calibration = Full
Water circulation signal= NC (normally closed)
Pump = ON (Enable)
Dosing type = PROP; ON/OFF Relay Aux1 e Aux2 only
Reset to the default parameters
Hold down the UP and DOWN arrows and switch the unit on.
Set reset routine:
Init. Default: restores the default settings of the device
Init. WiFi Module: restores the default settings of the WiFi
module
Init. Calib. HW: restores the default calibration settings
______Int. Default________
■ Init. Default
□ Init. WiFi Module
□ Init. Calib. HW
01/03