kVent – rel 3.1 – 22/06/2018
31
code
Description Type Default UoM Range R/W Variable Name BMS BacNet
Z00f Special month USInt 1
1...12 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[1].SpecialM
onth
HR66 PIV66
Z00f
Unit status of the special day (0=OFF;
1=ECONOMY; 2=PRE-COMFORT; 3=COMFORT;
4=AUTO)
USInt 0
0...4 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[1].UnitStatu
s
HR67 PIV67
Z00f Special day enabled Bool FALSE
0...1 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[2].Enabled
C10 BV95
Z00f Special day USInt 1
1...31 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[2].SpecialD
ay
HR68 PIV68
Z00f Special month USInt 1
1...12 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[2].SpecialM
onth
HR69 PIV69
Z00f
Unit status of the special day (0=OFF;
1=ECONOMY; 2=PRE-COMFORT; 3=COMFORT;
4=AUTO)
USInt 0
0...4 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[2].UnitStatu
s
HR70 PIV70
Z00f Special day enabled Bool FALSE
0...1 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[3].Enabled
C11 BV99
Z00f Special day USInt 1
1...31 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[3].SpecialD
ay
HR71 PIV71
Z00f Special month USInt 1
1...12 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[3].SpecialM
onth
HR72 PIV72
Z00f
Unit status of the special day (0=OFF;
1=ECONOMY; 2=PRE-COMFORT; 3=COMFORT;
4=AUTO)
USInt 0
0...4 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[3].UnitStatu
s
HR73 PIV73
Z00f Special day enabled Bool FALSE
0...1 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[4].Enabled
C12 BV103
Z00f Special day USInt 1
1...31 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[4].SpecialD
ay
HR74 PIV74
Z00f Special month USInt 1
1...12 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[4].SpecialM
onth
HR75 PIV75
Z00f
Unit status of the special day (0=OFF;
1=ECONOMY; 2=PRE-COMFORT; 3=COMFORT;
4=AUTO)
USInt 0
0...4 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[4].UnitStatu
s
HR76 PIV76
Z00f Special day enabled Bool FALSE
0...1 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[5].Enabled
C13 BV107
Z00f Special day USInt 1
1...31 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[5].SpecialD
ay
HR77 PIV77
Z00f Special month USInt 1
1...12 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[5].SpecialM
onth
HR78 PIV78
Z00f
Unit status of the special day (0=OFF;
1=ECONOMY; 2=PRE-COMFORT; 3=COMFORT;
4=AUTO)
USInt 0
0...4 R/W
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysSched[5].UnitStatu
s
HR79 PIV79
Z00f Messages to be displayed for special days USInt
R
Scheduler_OnOffUnit.Scheduler
_1.SpecDaysMsg
IR17 PIV17
Z021 Language DInt 0
0...4 R/W LangChange HR80 IV80
6.3 MODE menu in main mask
code
Description Type Defaut UoM Range R/W Variable Name BMS BacNet
X00a Current mode USInt
0
0...MaxSetTyp R/W SetTyp HR82 PIV82
X00a Machine status USInt
R OnOffStatus IR198 PIV198
X00b Boost function enable Bool
FALSE
R/W En_Boost_Function_Msk C344 BV1433
6.4 HEATING menu in main menu
code
- Heating device - Hardware value Bool
R Heat_1.HW_Val DI45 BV230
- Heating device - Value Bool
R Heat_1.Ctrl DI46 BV231
- Hours counter heating device UDInt
R HC_Heat_1.Hrs IR225 PIV225
A001 Hours counter heating device UDInt
0
0...999999 R/W HC_Heat_1.MaintThrsh HR169 PIV169
A002 Hours counter heating device Bool
0...1 R/W HC_Heat_1.Res C24 BV622
A003 Heating device - Manual value USInt
0...2 R/W Heat_1.Man HR171 PIV171
A004 Modulating heating output - Manual mode analog
output
USInt
0...101 R/W HeatVlv.Man HR172 PIV172
- Heating device 2nd step - Hardware value Bool
R Heat_2.HW_Val DI53 BV238
- Heating device 2nd step - Value Bool
R Heat_2.Ctrl DI54 BV239
- Hours counter heating 2nd step UDInt
R HC_Heat_2.Hrs IR227 PIV227
A005 Hours counter heating 2nd step UDInt
0
0...999999 R/W HC_Heat_2.MaintThrsh HR173 PIV173
A006 Hours counter heating 2nd step Bool
0...1 R/W HC_Heat_2.Res C25 BV627
A007 Heating device 2nd step - Manual value USInt
0...2 R/W Heat_2.Man HR175 PIV175
- Preheater - Hardware value Bool
R PreHeaterPump.HW_Val DI61 BV246
- Preheater - Value Bool
R PreHeaterPump.Ctrl DI62 BV247
- Hours counter preheating UDInt
R HC_PreHeat.Hrs IR229 PIV229
A008 Hours counter preheating UDInt
0
0...999999 R/W HC_PreHeat.MaintThrsh HR176 PIV176
A009 Hours counter preheating Bool
0...1 R/W HC_PreHeat.Res C26 BV631
A010 Preheater - Manual value USInt
0...2 R/W PreHeaterPump.Man HR178 PIV178
A011 Modulating preheating output - Manual mode USInt
0...101 R/W ModulPreHeat.Man HR179 PIV179