kVent – rel 3.1 – 22/06/2018
37
Ga45 Analog input functions - Offset Real
0.0
°K -99.9...99.9 R/W AI_ReadFnt[9].Param.Offset HR813 AV813
- Analog input functions - Priority USInt
R AI_ReadFnt[10].Prio IR354 PIV354
- Analog input functions - Hardware value Real
°C R AI_ReadFnt[10].Read.Hw_Val IR355 AV355
Ga46 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[10].Ch HR814 IV814
Ga47 Analog input functions - Type USInt
0
0...50 R/W AI_ReadFnt[10].Param.Typ HR816 PIV816
Ga48 Analog input functions - Minimum value Real
-50.0
°C -999.9...999.9 R/W AI_ReadFnt[10].Param.Min_Val HR817 AV817
Ga49 Analog input functions - Maximum value Real
105.0
°C -999.9...999.9 R/W AI_ReadFnt[10].Param.Max_Val HR818 AV818
Ga50 Analog input functions - Offset Real
0.0
°K -99.9...99.9 R/W AI_ReadFnt[10].Param.Offset HR819 AV819
- Analog input functions - Priority USInt
R AI_ReadFnt[11].Prio IR356 PIV356
- Analog input functions - Hardware value Real
°C R AI_ReadFnt[11].Read.Hw_Val IR357 AV357
Ga51 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[11].Ch HR820 IV820
Ga52 Analog input functions - Type USInt
0
0...50 R/W AI_ReadFnt[11].Param.Typ HR822 PIV822
Ga53 Analog input functions - Minimum value Real
-50.0
°C -999.9...999.9 R/W AI_ReadFnt[11].Param.Min_Val HR823 AV823
Ga54 Analog input functions - Maximum value Real
105.0
°C -999.9...999.9 R/W AI_ReadFnt[11].Param.Max_Val HR824 AV824
Ga55 Analog input functions - Offset Real
0.0
°K -99.9...99.9 R/W AI_ReadFnt[11].Param.Offset HR825 AV825
- Analog input functions - Priority USInt
R AI_ReadFnt[12].Prio IR358 PIV358
- Analog input functions - Hardware value Real
ppm R AI_ReadFnt[12].Read.Hw_Val IR359 AV359
Ga56 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[12].Ch HR826 IV826
Ga57 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[12].Param.Typ HR828 PIV828
Ga58 Analog input functions - Minimum value Real
0.0
ppm -99999.9...99999.9 R/W AI_ReadFnt[12].Param.Min_Val HR829 AV829
Ga59 Analog input functions - Maximum value Real
1000.0
ppm -99999.9...99999.9 R/W AI_ReadFnt[12].Param.Max_Val HR830 AV830
Ga60 Analog input functions - Offset Real
0.0
ppm -99.9...99.9 R/W AI_ReadFnt[12].Param.Offset HR831 AV831
- Analog input functions - Priority USInt
R AI_ReadFnt[13].Prio IR360 PIV360
- Analog input functions - Hardware value Real
Pa R AI_ReadFnt[13].Read.Hw_Val IR361 AV361
Ga61 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[13].Ch HR832 IV832
Ga62 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[13].Param.Typ HR834 PIV834
Ga63 Analog input functions - Minimum value Real
0.0
Pa -9999.9...9999.9 R/W AI_ReadFnt[13].Param.Min_Val HR835 AV835
Ga64 Analog input functions - Maximum value Real
1500.0
Pa -9999.9...9999.9 R/W AI_ReadFnt[13].Param.Max_Val HR836 AV836
Ga65 Analog input functions - Offset Real
0.0
Pa -99.9...99.9 R/W AI_ReadFnt[13].Param.Offset HR837 AV837
- Analog input functions - Priority USInt
R AI_ReadFnt[14].Prio IR362 PIV362
- Analog input functions - Hardware value Real
Pa R AI_ReadFnt[14].Read.Hw_Val IR363 AV363
Ga66 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[14].Ch HR838 IV838
Ga67 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[14].Param.Typ HR840 PIV840
Ga68 Analog input functions - Minimum value Real
0.0
Pa -9999.9...9999.9 R/W AI_ReadFnt[14].Param.Min_Val HR841 AV841
Ga69 Analog input functions - Maximum value Real
1500.0
Pa -9999.9...9999.9 R/W AI_ReadFnt[14].Param.Max_Val HR842 AV842
Ga70 Analog input functions - Offset Real
0.0
Pa -99.9...99.9 R/W AI_ReadFnt[14].Param.Offset HR843 AV843
- Analog input functions - Priority USInt
R AI_ReadFnt[15].Prio IR364 PIV364
- Analog input functions - Hardware value Real
%rh R AI_ReadFnt[15].Read.Hw_Val IR365 AV365
Ga71 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[15].Ch HR844 IV844
Ga72 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[15].Param.Typ HR846 PIV846
Ga73 Analog input functions - Minimum value Real
0.0
%rh -999.9...999.9 R/W AI_ReadFnt[15].Param.Min_Val HR847 AV847
Ga74 Analog input functions - Maximum value Real
100.0
%rh -999.9...999.9 R/W AI_ReadFnt[15].Param.Max_Val HR848 AV848
Ga75 Analog input functions - Offset Real
0.0
%rh -99.9...99.9 R/W AI_ReadFnt[15].Param.Offset HR849 AV849
- Analog input functions - Priority USInt
R AI_ReadFnt[16].Prio IR366 PIV366
- Analog input functions - Hardware value Real
bar R AI_ReadFnt[16].Read.Hw_Val IR367 AV367
Ga76 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[16].Ch HR850 IV850
Ga77 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[16].Param.Typ HR852 PIV852
Ga78 Analog input functions - Minimum value Real
0.0
bar -9999.9...9999.9 R/W AI_ReadFnt[16].Param.Min_Val HR853 AV853
Ga79 Analog input functions - Maximum value Real
45.0
bar -9999.9...9999.9 R/W AI_ReadFnt[16].Param.Max_Val HR854 AV854
Ga80 Analog input functions - Offset Real
0.0
bar -99.9...99.9 R/W AI_ReadFnt[16].Param.Offset HR855 AV855
- Analog input functions - Priority USInt
R AI_ReadFnt[17].Prio IR368 PIV368
- Analog input functions - Hardware value Real
°C R AI_ReadFnt[17].Read.Hw_Val IR369 AV369
Ga81 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[17].Ch HR856 IV856
Ga82 Analog input functions - Type USInt
0
0...50 R/W AI_ReadFnt[17].Param.Typ HR858 PIV858
Ga83 Analog input functions - Minimum value Real
-50.0
°C -999.9...999.9 R/W AI_ReadFnt[17].Param.Min_Val HR859 AV859
Ga84 Analog input functions - Maximum value Real
105.0
°C -999.9...999.9 R/W AI_ReadFnt[17].Param.Max_Val HR860 AV860
Ga85 Analog input functions - Offset Real
0.0
°K -99.9...99.9 R/W AI_ReadFnt[17].Param.Offset HR861 AV861
- Analog input functions - Priority USInt
R AI_ReadFnt[18].Prio IR370 PIV370
- Analog input functions - Hardware value Real
bar R AI_ReadFnt[18].Read.Hw_Val IR371 AV371
Ga86 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[18].Ch HR862 IV862
Ga87 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[18].Param.Typ HR864 PIV864
Ga88 Analog input functions - Minimum value Real
0.0
bar -9999.9...9999.9 R/W AI_ReadFnt[18].Param.Min_Val HR865 AV865
Ga89 Analog input functions - Maximum value Real
17.3
bar -9999.9...9999.9 R/W AI_ReadFnt[18].Param.Max_Val HR866 AV866
Ga90 Analog input functions - Offset Real
0.0
bar -99.9...99.9 R/W AI_ReadFnt[18].Param.Offset HR867 AV867
- Analog input functions - Priority USInt
R AI_ReadFnt[19].Prio IR372 PIV372
- Analog input functions - Hardware value Real
°C R AI_ReadFnt[19].Read.Hw_Val IR373 AV373
Ga91 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[19].Ch HR868 IV868
Ga92 Analog input functions - Type USInt
0
0...50 R/W AI_ReadFnt[19].Param.Typ HR870 PIV870
Ga93 Analog input functions - Minimum value Real
-50.0
°C -999.9...999.9 R/W AI_ReadFnt[19].Param.Min_Val HR871 AV871
Ga94 Analog input functions - Maximum value Real
105.0
°C -999.9...999.9 R/W AI_ReadFnt[19].Param.Max_Val HR872 AV872
Ga95 Analog input functions - Offset Real
0.0
°K -99.9...99.9 R/W AI_ReadFnt[19].Param.Offset HR873 AV873
- Analog input functions - Priority USInt
R AI_ReadFnt[20].Prio IR374 PIV374
- Analog input functions - Hardware value Real
bar R AI_ReadFnt[20].Read.Hw_Val IR375 AV375
Ga96 Analog input functions - Channel DInt
0
0...70 R/W AI_ReadFnt[20].Ch HR874 IV874
Ga97 Analog input functions - Type USInt
43
0...50 R/W AI_ReadFnt[20].Param.Typ HR876 PIV876
Ga98 Analog input functions - Minimum value Real
0.0
bar -9999.9...9999.9 R/W AI_ReadFnt[20].Param.Min_Val HR877 AV877
Ga99 Analog input functions - Maximum value Real
45.0
bar -9999.9...9999.9 R/W AI_ReadFnt[20].Param.Max_Val HR878 AV878
GaA0 Analog input functions - Offset Real
0.0
bar -99.9...99.9 R/W AI_ReadFnt[20].Param.Offset HR879 AV879
- Analog input functions - Priority USInt
R AI_ReadFnt[21].Prio IR376 PIV376