15
rel. 2.7 - 16.11.2018
ENG
"Passive probes" +030220658 -
3.2 Models TSC1500030
Immersion probes feature the sensor directly in contact with the liquid and are secured to the tubing using a connector, available in the screw or weldable
versions.
The body is nickel-coated brass, index of protection IP67, and the gasket (O-ring) is supplied together with the probe.
Storage conditions -40T90 °C
Operating range -40T90 °C
Sensor NTC 10 kΩ ±1% at 25 °C Beta 3435
Construction Direct immersion with connection to M14 male process fitting
Cable 2 wires AWG 22, with TPE sheath
Thermal constant over time approx. 5 s in water - 45 s in air
Sensitive element housing Nickel-coated brass & grey PA6 co-moulded body
Insulation 100 Mohm at 100 Vdc
Maximum operating pressure 25 bar
Compatible liquids Water
Tab. 3.b
Key:
1 sensitive element
2 nickel-coated brass locking ring
3 co-moulded body
4 cable marking
5 tinned copper 2-wire cable
6 NTC sensor
7 2015 O-ring
8 nickel-coated brass thermome-
ter socket
23
EX14
~7.5
~40
15