36
rel. 2.7 - 16.11.2018
ENG
"Passive probes" +030220658 -
13. TEMPERATURE SENSOR INSTALLATION INSTRUCTIONS
1
2
3
1. welding of socket to pipe
2. closed end of socket at top
3. tubular section ID 6 mm - min. length 70 mm
Weld the socket so as to create good thermal contact.
1 2
4
4. conductive paste
Fill the socket with conductive paste.
0,2...0,3 m
Insert the sensor completely into the socket.
Wrap 0.2-0.3 m of cable around the pipe.
10 cm
0,2...0,3 m
Make sure the contact area is thermally insulated.
Note: if installing on a horizontal pipe, the same precautions apply,
however without restrictions for the closed end of the socket.
3
4
5