11
Cooling Test
The COOL submenu is used to change output status for the
individual compressors and Humidi--MiZer system operation. The
HEAT submenu service test outputs are reset to OFF for the
cooling service test. Indoor fans and outdoor fans are controlled
normally to maintain proper unit operation when set for automatic
transition. The IDF SPEED TEST and ALL ODFSPD TEST can
be changed as needed for testing. These fans points show the
requested speed not actual speed. All normal cooling faults and
alerts are functional.
Heating Test
The HEAT submenu is used to change output status for the
individual heat stages, gas or electric. The COOL service test
outputs are reset to OFF for the heating service test. Indoor fan is
controlled normally to maintain proper unit operation when set for
automatic transition. The IDF SPEED TEST can be changed as
needed for testing and shows the requested speed not actual speed.
All normal heating faults and alerts are functional.
NOTE: When the IGC fan on command (IGC FAN REQUEST)
is active the fan may run when not expected.
Table 4 – Test Mode Unit Test Directory
Display Menu/Sub menu/Name Expan de d Na me Values
UNIT TESTS Unit Tests Menu
TEST MODE ServiceTestModeEnable Off/On
SERVICE TEST Service Test Menu
INDEPENDENTS INDEPENDENT TEST MENU
ECON POS TEST Economizer Position Test 0 to 100
BUMP COMP A1 TEST Compressor Bump A1 Test Off/On
RH DIS VALVE TEST Rht Dischg Valve Rly Tst Off/On
RH LIQ VALVE TEST Reheat Liq Valv Rly Test Off/On
CL LIQ VALVE TEST Cooling Liq Valv Test Off/On
CCH RELAY 1 TEST Crankcase Heater 1 test Off/On
ALARM RELAY TEST Alarm Output Relay Test Off/On
PE1 RELAY TEST Power Exhaust 1 T est Off/On
PE2 RELAY TEST Power Exhaust 2 T est Off/On
2POS/ERV RLY TEST 2Position/ERV Relay Test Off/On
FAN TESTS Ind oor and Outdoor Fan tests
IDF SPEED TEST Indoor Fa n Speed Test 0 to 100
CONVERTED IDF RPM Converted IDF Speed XXXX
IDF MANUAL TRANS IDF Manual Transition Ye s/No
COOL Cooling Status Menu
COOL A1 TEST Cooling W/Comp.A1 Test Off/On
CIR A LOADER TEST Cooling W/Comp.ALD Test Off/On
IDF SPEED TEST Indoor Fa n Speed Test 0 to 100
ODF RELAY TEST ODF Speed Relay Test Off/On
HUMIDIMIZER TEST Humidimizer Level Test 0=Off
1 = SUBCOOL
2=REHEAT
HEAT Heating Status Menu
HEAT 1 TEST Heating Stage 1 Test Off/On
HEAT 2 TEST Heating Stage 2 Test Off/On
IDF SPEED TEST Indoor Fa n Speed Test 0 to 100
AUTOMATIC TEST Automatic Test Menu
AUTO INDP TEST AUTO INDEPENDENT TEST Yes/No
AUTO COOL TEST RUN AUT O COOLING TEST Yes/No
AUTO HEAT TEST RUN AUTO HEATING TEST Yes/No
AUTO SYSTEM TEST RUN AUTO SYSTEM TEST Yes/No
Automatic Test
The AUTOMATIC TEST sub m enu is u sed to ex ecute all th e
app licable tests to th e sy stem au to m atically. Th ese in clu d e
independent components, cooling, heating, and system. Table 5
shows the steps taken during the independent, cooling, and
heatin g au to m atic tests. Th e Hold time rep resen ts the time at
which that control waits before moving on to the next step.
The AUTO SYSTEM TEST will execute the independent auto
test, then the cooling auto test, then the heating auto test. At the end
of the system auto test a prompt will ask if you want to enter
measured data and complete a service report.
Table 5 – Independent, Cooling, and Heating Automatic Tests
AUTO INDP TEST
Step Action Hold (Sec)
1 Turn on Crankcase Heater Relay 0
2 Set IDF speed to 100% 30
3 Turn on 2 position damper/ERV relay 30
4 Set Economizer Damper to 100% 60
5 Turn on power e x h aust 1 10
6 Turn on power e x h aust 2 10
7 SetEconomizerDamperto0% 60
8 Turn off power exhaust 2 10
9 Turn off power exhaust 1 10
10 Set IDF to the ventilation speed 30
11 Turn off 2 position damper/ERV relay 0
12 Tu rn on alarm relay 10
13 Turn off alarm relay 10
14 Set IDF to 0% speed 30
15 Turn off Crankcase Heater relay 0
AUTO COOL TEST
Step Action Hold (Sec)
1 Set IDF auto transition 0
2 Turn on Cool A1 test 60
3 Turn on Compressor Loader test 30
4 Turn off ODF Rel a y test 10
5 Turn off Compressor Loader test 60
6 Turn off Cool A1 test 30
7 Turn on Hot Gas Reheat Test 60
8 Switch to Subcooling Test 30
9 Turn off Su bcooling Test 30
AUTO HEAT TEST
Step Action Hold (Sec)
1 Set IDF auto transition 0
2 Turn on Heat 1 test 60
3 Turn on Heat 2 test 60
4 TurnoffHeat1andHeat2tests 20