APPENDIX D: SystemVut Controller CCN Tables
Setpoint Table
TABLE NAME DISPLAY NA ME VA L UES UNITS POINT NAME DEFA ULT
SET_PNT
Occupied Cool Setpoint 55 to 80 °F OCSP 78
Occupied Heat Setpoint 55 to 80 °F OHSP 68
Unoccupied Cool Setpoint 65 to 95 °F UCSP 85
Unoccupied Heat Setpoint 40 to 80 °F UHSP 60
Heat--- Cool Setpoint Gap 2to10 ^F HCSP_GAP 5
SPT Offset Range (+/--- ) 0to5 °F SPTO_RNG 5
Occupied SPRH Setpoint 0 to 100 % SPRH_OSP 55
Unoccupied SPRH Setpoint 0 to 100 % SPRH_USP 55