APPENDIX E: BACnet Points List
Analog Value (AV) Points (cont)
POINT DESCRIPTION POINT ACCESS UNITS
BACnet OBJECT
NAME
BACnet ID VALUE RANGE
CCN POINT
EQUIVALENT
Heat Stage 1 Timeguard READ ONLY sec timgd_h1 AV:173 0 TO 600 TIMGD_H1
Heat Stage 2 Reset Count READ ONLY rs_htr_2 AV:107 0 TO 65535 RS_HTR_2
Heat Stage 2 Run Hours READ ONLY hrs hour_ht_2 AV:55 0 TO 999999 HR_HTR_2
Heat Stage 2 Starts READ ONLY st_htr_2 AV:143 0 TO 999999 ST_HTR_2
Heat Stage 2 Timeguard READ ONLY sec timgd_h2 AV:50 0 TO 600 TIMGD_H2
Heat--- Cool Setpoint Gap R/W °F hcsp_gap AV:238 2TO10 HC SP_GAP
Heating Fan--- Off Delay R/W sec heat_fod AV:241 10 TO 600 HEAT_FOD
Heating Lockout Temp R/W °F oatlheat AV:8033 40 TO 125 OATLHEAT
Heating Space Demand READ ONLY °Fdelta heat_dmd AV:240 --- 100 TO 100 HEAT_DMD
High Cool Demand On R/W °F dmdhcon AV:215 0.5 TO 20 DMDHCON
High FreeCool SAT Setpnt R/W °F high_cool_sasp AV:237 40 TO 80 HCSASP
High Heat Demand On R/W °F dmdhhon AV:217 0.5 TO 20 DMDHHON
HumidiMizer Level Test R/W s_hmzlev AV:414 0TO2 S_HMZLEV
IAQ Assigned Channel R/W iaq_channel AV:7 0TO3 IAQ_CHAN
IAQ DCV Curve --- Pos 1 READ ONLY % aq_pos1 AV:196 0TO1 AQ_POS1
IAQ DCV Curve --- Pos 2 READ ONLY % aq_pos2 AV:197 0TO1 AQ_POS2
IAQ DCV Curve --- Pos 3 READ ONLY % aq_pos3 AV:198 0TO1 AQ_POS3
IAQ DCV Curve --- Speed 1 READ ONLY % aq_spd1 AV:199 0TO1 AQ_SPD1
IAQ DCV Curve --- Speed 2 READ ONLY % aq_spd2 AV:200 0TO1 AQ_SPD2
IAQ DCV Curve --- Speed 3 READ ONLY % aq_spd3 AV:201 0TO1 AQ_SPD3
IAQ DCV Curve Offset READ ONLY % iaq_offs AV:245 0TO1 IAQ_OFFS
IAQ Position at Max Fan R/W % iaqminp AV:246 0TO1 IAQMINP
I A Q P u r g e C u r v e --- P o s 1 READ ONLY % aqp_pos1 AV:358 0TO1 AQP_POS1
I A Q P u r g e C u r v e --- P o s 2 READ ONLY % aqp_pos2 AV:359 0TO1 AQP_POS2
I A Q P u r g e C u r v e --- P o s 3 READ ONLY % aqp_pos3 AV:360 0TO1 AQP_POS3
I A Q P u r g e C u r v e --- S p e e d 1 READ ONLY % aqp_spd1 AV:361 0TO1 AQP_SPD1
I A Q P u r g e C u r v e --- S p e e d 2 READ ONLY % aqp_spd2 AV:362 0TO1 AQP_SPD2
I A Q P u r g e C u r v e --- S p e e d 3 READ ONLY % aqp_spd3 AV:363 0TO1 AQP_SPD3
IAQ Purge Curve Offset READ ONLY % aqp_offs AV:364 0TO1 AQP_OFFS
IAQ Sensor Value at 20mA R/W PPM iaq_20ma AV:12 0 TO 5000 IAQ_20MA
IAQ Sensor Value at 4mA R/W PPM iaq_4ma AV:13 0 TO 5000 IAQ_4MA
IDF Commanded RPM R/W RPM fspd_rpm AV:8048 0 TO 5000 FSPD_RPM
IDF Free Cool Speed --- RPM R/W RPM rpm_fcl AV:8050 0 TO 5000 RPM_FCL
IDF Heat Speed --- RPM R/W RPM rpm_heat AV:8052 0 TO 5000 RPM_HEAT
IDF High Cool Speed---RPM R/W RPM rpm_hcl AV:8051 0 TO 5000 RPM_HCL
IDF Low Cool Speed--- RPM R/W RPM rpm_lcl AV:8053 0 TO 5000 RPM_LCL
IDF Maximum Fan Speed R/W % speed_max AV:36 0.8 TO 1 SPEEDMAX
IDF Vent Speed --- RPM R/W RPM rpm_vent AV:8054 0 TO 5000 RPM_VENT
Indoor Air Quality Level R/W PPM iaq AV:1009 0 TO 5000 IAQ
Indoor Fan Reset Count READ ONLY rs_idf AV:108 0 TO 65535 RS_IDF
Indoor Fan Run Hours READ ONLY hrs hour_idf AV :56 0 TO 999999 HR_IDF
Indoor Fan Speed Test R/W % s_idfspd AV:119 0TO1 S_IDFSPD
Indoor Fan Starts READ ONLY st_idf AV:144 0 TO 999999 ST_IDF
Linkage CCN Bus number R/W lnk_supb AV:272 0 TO 239 LNK_SUPB
Linkage CCN element # R/W lnk_supe AV:273 0 TO 239 LNK_SUPE
Linkage Cooling Required READ ONLY °F lnk_creq AV:257 0TO30 LNK_CREQ
Linkage Damper Position READ ONLY % lnk_dpos AV:258 0TO1 LNK_DPOS
Linkage Equipment Mode READ ONLY lnk_mode AV:261 0TO8 LNK_MODE
Linkage Heating Required READ ONLY °F lnk_hreq AV:259 0TO30 LNK_HREQ
Linkage Maximum Airflow READ ONLY lnk_mair AV:260 0 TO 5000 LNK_MAIR
Linkage Optimal Start READ ONLY min lnk_opst AV:267 0 TO 180 LNK_OPST
Linkage Space Air Qual. READ ONLY PPM lnk_siaq AV:270 0 TO 2000 LNK_SIAQ
Linkage Space RH READ ONLY % lnk_sprh AV:271 0TO1 LNK_SPRH
Linkage Start Bias time R/W min lnk_sbt AV:269 0 TO 180 LNK_SBT
Linkage static pressure READ ONLY IN_H2O link_ahu_static AV:312 --- 5 T O 5 LNK_DSP
Linkage Supply air temp READ ONLY °F lnk_sat AV:268 --- 40 TO 240 LNK_SAT
Local Std Time offset R/W min utc_ofst AV:191 --- 780 TO 780 UTC_OFST
Low Charge Disable Temp R/W °F loch_lot AV:276 --- 40 TO 50 LOCH_LOT
Low Cool Demand Off R/W °F dmdlcoff AV:218 --- 1 T O 2 DMDLCOFF
Low Cool Demand On R/W °F dmdlcon AV:219 --- 1 T O 2 DMDLCON
Low Cool Lockout Temp R/W °F lclocksp AV:8031 --- 20 TO 60 LCLOCKSP
Low Heat Demand Off R/W °F dmdlhoff AV:220 --- 1 T O 2 DMDLHOFF
Low Heat Demand On R/W °F dmdlhon AV:221 --- 1 T O 2 DMDLHON
Low Refrig Charge Level R/W PSI locharge AV:277 0 TO 150 LOCHARGE