139
Settings -- Main Menu Layout (cont)
DISPLAY TEXT EXP ANDED DISPLAY TEXT VALUES UNITS DEFAUL T POINT ENTRY
SERVI CE CONFIG MENU (cont) Service Configuration Menu
IDF CURVE HI RPM IDF Curve High End RPM 0 to 3000 RPM 1890: Size 04 Standard
Static Fan
2190: Size 04 Medium
Static Fan
2490: Size 04 High
Static Fan
1900: Size 05 Standard
Static Fan
2170: Size 05 Medium
Static Fan
2460: Size 05 High
Static Fan 230v
1ph
2660: Size 05 High
Static Fan 230v
3ph, 460v, 575v
2150: Size 06 Standard
Static Fan
2390: Size 06 Medium
Static Fan
2660: Size 06 High
Static Fan 230v
1ph
2836: Size 06 High
Static Fan 230v
3ph, 460v, 575v
2300: Size 07 Standard
Static Fan
2530: Size 07 Medium
Static Fan
2836: Size 07 High
Static Fan
IFMHIRPM
CCH RELAY1 ENABLE CCH Relay 1 Enabled Ye s/ No Yes CCHR1_EN
E C O N O P I D --- K P E C O N O P I D --- K P 0.00 to 99.90 2.5 ECONO_P
E C O N O P I D --- K I E C O N O P I D --- K I 0.00 to 99.90 0.12 ECONO_I
E C O N O P I D --- K D E C O N O P I D --- K D 0.00 to 99.90 1 ECONO_D
E C O N O P I D --- R A T E E C O N O P I D --- R AT E 10 to 180 sec 15 ECONO_DT
F B D P I D --- K P F B D P I D --- K p 0 to 99.99 0.01 FBDPID_P
F B D P I D --- K I FBD PID Ki 0 to 99.999 0 FBDPID_I
F B D P I D --- K D FBD PID Kd 0 to 99.999 0 FBDPID_D
FBD KI RES VAL FBD Ki Reset Val. 0.00 to 99.90 0 FBDKIRES
NEW HARDWARE Quick Menu for New Hardware
UNIT CONTROL TYPE Unit Control Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
0=NONE SPRHCHAN
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
2: FIOP
IAQ_CHAN
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE OAQ_CHAN
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
3: FIOP
OARHCHAN
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE RARHCHAN
OACFM SENS CHANNEL OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=NONE OCFMCHAN
FIRE SHUTDOWN SW Fire Shutdown Switch 0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
HUMSTAT CHANNEL Humidistat Status Chan. 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
0 : N o H u mi d i --- MiZ e r
FIOP
5 : H u mi d i --- M i Ze r F IOP
HUMDCHAN
FILTER SW CHANNEL Filter Status Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
0: No FIOP
1: FIOP
FILTCHAN
REMOTE OCC CHAN Remote Occupancy Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
0=NONE RM OCCHAN