66
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
DISPLAY TEXT EXPANDED DISPLAY TEXT VALUES UNITS DEFAULT POINT
ANALOG INPUT CONFIGS Analog Inputs Configuration Menu
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE SPRHCHAN
SPRH RH @ 4MA SPRH Sensor Value at 4mA 0 to 100 % 0 SPRH_4MA
SPRH RH @ 20MA SPRH Sensor Value @ 20mA 0 to 100 % 100 SPRH20MA
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: No FIOP
2: FIOP
IAQ_CHAN
IAQ PPM @ 4MA IAQ Sensor Value at 4mA 0 t o 5000 PPM 0 IAQ_4MA
IAQ PPM @ 20MA IAQ Sensor Value at 20mA 0 t o 5000 PPM 2000 IAQ_20MA
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE OAQ_CHAN
OAQ PPM @ 4MA OAQ Sensor Value at 4mA 0 to 5000 PPM 0 OAQ_4MA
OAQ PPM @ 20MA OAQ Sensor Value at 20mA 0 to 5000 PPM 2000 OAQ_20MA
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: No FIOP
3: FIOP
OARHCHAN
OARH RH @ 4MA OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OARH RH @ 20MA OARH Sensor Val. at 20mA 0 to 100 % 100 OARH20MA
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE RARHCHAN
RARH RH @ 4MA RARH Sensor Value at 4mA 0 t o 100 % 0 RARH_4MA
RARH RH @ 20MA RARH Sensor Value @ 20mA 0 to 100 % 100 RARH20MA
OACFM SENSOR CHAN OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=NONE OCFMCHAN
OACFM @ 4MA OACFM value at 4MA 0 to 2000 CFM 0 OCFM_4MA
OACFM @ 20MA OACFM Value @ 20mA 2000 to 5000 CFM 2000 OCFM20MA
COOLING Cooling Configurations Menu
COMP MIN ON TIME Compressor Min On Time 180 to 600 sec 300 C_MINON
COMP MIN OFF TIME Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
STRIKE CLEAR TIME Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
COOL STAGEUP TIME Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
COOL SATTREND LEV Cooling SAT Trend Level --- 1 t o 1 --- 0 . 2 SAT_TLC
UPPER MIN SAT Cool Min SAT Upper Level 35.0 to 65.0 °F 56 SATMIN_H
LOWER MIN SAT Cool Min SAT Lower Level 35.0 to 65.0 °F 46 SATMIN_L
COOL FANOFF DELAY Cooling Fan--- Off Delay 0 t o 600 sec 75: All except below
30: Size 07
90: 48/50GC 06
COOL_FOD
ODF HIGH SPD TIME ODF H igh Speed Time 0 to 300 sec 120 MINODFTM
ODF RELAY ENABLE ODF Relay Enabled Ye s/No No: 48/50FC
Yes: 48/50GC
OFR_EN
DEHUMIDIFICATION DEHUMIDIFICATION
REHEAT EQUIPPED Humidimizer Equipped Ye s/No N o : N o H u m i d i --- M i Z e r
FIOP
Ye s : H u m i d i --- M i Z e r F I O P
HUMZ_EN
REHEAT OAT LIMIT Humidimizer Lockout Temp --- 20 to 75 °F 40 OATLHUMZ
FAN BASED DEHUM Fan Based Dehum CFG Menu
FBD CONTROL TYPE Fan Based Dehum Type 0=NONE,
1=Comfort,
2=Max
0=NONE FBD_TYPE
FBD COOL DELTA FBDH Low Set Point --- 2 0 t o 0 ΔF --- 2 . 5 FBDLO_SP
FBD MAX SST SP FBDH Max Mode SST SP 20 to 60 °F 38 FBDSSTSP
FBD SST MIN VALUE FBDH Min SST Threshold 10 to 60 °F 32 FBDH_SST
FBD CMFT SAT SP FBDH Comfort SAT SP 35 to 80 °F 46 FBDH_SAT
FBD CMFT SAT DT FBD Comfort SAT Delta 0to30 °F 11 FBDSATDT
FBD MIN FAN SPD FBDH Min Fan Speed 0 to 3000 RPM same as IDF LOW COOL
SPD (page 68)
FDRPMMIN
FBD MAX FAN SPD FBDH Max Fan Speed 0 to 3000 RPM same as IDF HIGH
COOL SPD (page 68)
FDRPMMAX