4 - ACCESS LEVEL (MENU 8)
The CCU CONTROLLER has 3 access levels, two of which require an access code. The various levels are accessed using menu 8 
in the unit's menu. 
 ■ Access to level 1 (No access code)
This is a general level designed for the end user. This level gives access to all the reading parameters and the settings for the main 
setpoints and proportional bands: 
 - Cooling 
 - Heating 
 - Humidication 
 - Dehumidication 
 - Supply air temperature limits 
 - Temperature and humidity limit thresholds 
 - Filter check. 
It also allows the language, date and time to be altered.
 ■ Access to level 2 (editable numeric code)
This level is designed for installers and experienced users. It gives access to the following functionalities: 
 - Free cooling
 - On/off control and conguration lock 
 - Fixed offsets during heating/cooling 
 - Limits relating to the speed variations of the forced-draught fans 
 - Time delay settings 
 - CMS communication parameter settings 
 ■ Access to level 3 (non-editable numeric code)
This level is designed for the manufacturer's operators and for factory settings. It gives access to all parameters of the control.