6 - CONFIGURING THE UNIT
6.2.3 - Alarm (sub-menu 9.3)
Alarm Description
The humidier has no fault
Mn Replace the cylinder
EC Water conductivity too high
E1 Conguration parameter error
E0 Internal memory error
EH Electrode overcurrent
EP Low steam ow rate during reduced production
EU Water level raised without humidication request
EF Lack of supply water
ED Drain problem
To acknowledge a fault on the humidier, go to the "ALARM" menu (menu 9.3) and press the "Reset" key
6.3 - Supply air fan parameters (visible if P05 = 1 or 2 or 3)
6.3.1 - FMA1 information (sub-menu 10.1)
Access level No. Description Unit Display condition
1 1000 FMA1 max. speed rpm P05 = 1, 2 or 3
1 1001 FMA1 requested speed rpm P05 = 1, 2 or 3
1 1002 FMA1 current speed rpm P05 = 1, 2 or 3
1 1003 FMA1 current consumed A P05 = 1, 2 or 3
1 1004 FMA1 peak supply voltage V P05 = 1, 2 or 3
1 1005 FMA1 power input W P05 = 1, 2 or 3
1 1010 FMA1 fault summary Off/On P05 = 1, 2 or 3
1 1011 FMA1 start-up fault Off/On P05 = 1, 2 or 3
1 1012 FMA1 rotation direction fault Off/On P05 = 1, 2 or 3
1 1013 FMA1 current limitation Off/On P05 = 1, 2 or 3
1 1014 FMA1 temperature limitation Off/On P05 = 1, 2 or 3
1 1015 FMA1 off Off/On P05 = 1, 2 or 3
1 1020 FMA1 internal DC voltage V P05 = 1, 2 or 3
1 1021 FMA1 IGBT temperature °C P05 = 1, 2 or 3
1 1022 FMA1 indoor room temperature °C P05 = 1, 2 or 3
1 1023 FMA1 MCU temperature °C P05 = 1, 2 or 3
1 1048 FMA1 product code P05 = 1, 2 or 3
1 1049 FMA1 software version P05 = 1, 2 or 3