15.4 - Precision air conditioning controller
Registers accessible to customer
Register No.
Description
Mnemonic
BACnet
object
Read/Write Format
Unit/
Enumeration
AHU no.1 – AHU_1.mnemonique
3 and 4
Outdoor temperature (P258)
OutdoorTemp AV0002 R Float °C
5 and 6
Controlled temperature (P255)
TempRegulee AV0001 R Float °C
7 and 8
Controlled humidity (P256)
HygroRegulee AV0015 R Float % RH
13 and 14
Outdoor humidity (P265)
OutdoorHygro AV0003 R Float % RH
257 and 258
Cooling temperature setpoint (P103)
CoolSetpt AV0007 R/W Float °C
259 and 260
Heating temperature setpoint (P106)
HeatSetpt AV0004 R/W Float °C
5382 and 5383
Filter differential pressure (P257)
PresDifFiltre AV0010 R Float Pa
5384 and 5385
Supply air temperature (P259)
TempSouff AV0011 R Float °C
5428 and 5427
Raised floor differential pressure (P266)
PresPlancher AV0009 R Float Pa
48
Heating coil percentage (P291)
PourBatChaud AV0022 R Word %
49
Cooling coil percentage (P292)
PourBatFroid AV0021 R Word %
50
Humidifier percentage (P294)
PourHumidif AV0024 R Word %
51
Air flow rate percentage (P295)
PourDebitAir AV0020 R Word %
52
Fresh air percentage (P296)
PourAirNeuf AV0025 R Word %
53 Electric heater percentage (P297) PourBatElec AV0023 R Word %
261
Humidity setpoint during dehumidification (P109)
DeshuSetpt AV0005 R/W Word % RH
262
Humidity setpoint during humidification (P115)
HumidSetpt AV0006 R/W Word % RH
4638
Rotation speed percentage (P155)
FanSpeedCmd AV0008 R/W Word %
AHU no.2 – AHU_2.mnemonique
3 and 4
Outdoor temperature (P258)
OutdoorTemp AV0052 R Float °C
5 and 6
Controlled temperature (P255)
TempRegulee AV0050 R Float °C
7 and 8
Controlled humidity (P256)
HygroRegulee AV0051 R Float % RH
13 and 14
Outdoor humidity (P265)
OutdoorHygro AV0053 R Float % RH
257 and 258
Cooling temperature setpoint (P103)
CoolSetpt AV0057 R/W Float °C
259 and 260
Heating temperature setpoint (P106)
HeatSetpt AV0054 R/W Float °C
5382 and 5383
Filter differential pressure (P257)
PresDifFiltre AV0060 R Float Pa
5384 and 5385
Supply air temperature (P259)
TempSouff AV0061 R Float °C
5428 and 5427
Raised floor differential pressure (P266)
PresPlancher AV0059 R Float Pa
48
Heating coil percentage (P291)
PourBatChaud AV0071 R Word %
49
Cooling coil percentage (P292)
PourBatFroid AV0070 R Word %
50
Humidifier percentage (P294)
PourHumidif AV0073 R Word %
51
Air flow rate percentage (P295)
PourDebitAir AV0069
R
Word %
52
Fresh air percentage (P296)
PourAirNeuf AV0074 R Word %
53
Electric heater percentage (P297)
PourBatElec AV0072 R Word %
261
Humidity setpoint during dehumidification (P109)
DeshuSetpt AV0055 R/W Word % RH
262
Humidity setpoint during humidification (P115)
HumidSetpt AV0056 R/W Word % RH
4638
Rotation speed percentage (P155)
FanSpeedCmd AV0058 R/W Word %