EasyManuals Logo

Carrier SPS User Manual

Carrier SPS
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
SPT sensors
Carrier Sensors 9
Feature
Usage
WARMER and COOLER
buttons
To raise or lower the zone's setpoint:
1 Press either button to display the current average setpoint (the average
between the heating and cooling setpoints).
2 Press either button again to raise or lower the setpoint. You can adjust the
setpoint by no more than the amount defined in the
Max Adjust
field*.
NOTE
Pressing either button overrides an unoccupied schedule and sets the
zone to occupied for the amount of time defined in the
Each pulse
field*.
INFO button
Press to cycle through the:
zone temperature
outside air temperature, if enabled in the control program
override time, in minutes
heating setpoint
cooling setpoint
* See To change sensor properties (page 9).
SPT Pro Plus
The SPT Pro Plus has all the features of the SPT Pro plus the additional functionality described below.
Feature
Usage
MANUAL ON button
The
Timed Local Override
section of the microblock dialog box determines if
pressing the
MANUAL ON
button sets the zone to occupied for a set amount of
time in the same manner as the RS Pro or sets the zone to continuously
occupied.
INFO button
This button cycles through the same information as the RS Pro and up to 4
additional inputs defined in the
Optional Inputs
section of the microblock dialog
box in EIKON LogicBuilder.
MODE button
The
MODE
button lets you cycle through up to 4 operational modes defined with
custom programming. The sensor displays information for each mode based on
the setup in the
Mode
section of the microblock dialog box.
FAN button
Press
FAN
to select the controlled equipment's fan speed. A fan icon on the left
side of the display indicates when the fan is on.
To change sensor properties
You can use the following items, if included with your system, to change sensor properties such as the
override time or maximum setpoint adjustment:
i-Vu Open
Field Assistant
BACview or Virtual BACview
Field Assistant and Virtual BACview run on a laptop that you connect to an SPT sensor's Local Access port.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier SPS and is the answer not in the manual?

Carrier SPS Specifications

General IconGeneral
BrandCarrier
ModelSPS
CategorySecurity Sensors
LanguageEnglish

Related product manuals