CO2 sensor   
 
32  Carrier Sensors 
 
   
 
 
To wire and duct-mount the sensor 
Duct installation requires the Aspirator Box Accessory (Part #33ZCASPCO2) to house the CO
2 
sensor.  
3.5 in.
(8.9 cm)
7.1 in.
(18 cm)
1.2 in.
(3.05 cm)
4.31 in.
(11 cm)
5.5 in.
(14 cm)
3.54 in.
(9 cm)
3.5 in.
(8.99 cm)
3.5 in.
(8.99 cm)
1.77 in.
(4.59 cm)
7.75 in.
(20 cm)
1.1 in.
(2.8 cm)
.25 in. dia.
(.64 cm dia.)
#33ZCASPCO2
aspirator box
 
 
To mount the aspirator box and sensor: 
1  Drill a 1.25 inch (3.18 cm) hole in the return duct. 
2  Remove the aspirator box cover. 
3  Insert the aspirator box sampling tube into the hole. 
4  Secure the box to the duct using 2 field-supplied #8 x 1" sheet metal screws. 
5  Remove .5 inch (1.3 cm) conduit knockout, then install the conduit fittings. 
6  Mount the CO
2
 sensor in the aspirator box using 2 field-supplied #8 x 32 machine screws. 
7  To wire the CO
2
 sensor, see the instructions above in To wire and wall-mount the CO
2
 sensor (page 31). 
8  Install the aspirator box cover.