Relative Humidity sensors   
 
38  Carrier Sensors 
 
 
 
Outdoor Relative 
Humidity sensor
 
Part #33ZCSENORH-01 
Measures outdoor 
humidity. 
 
CAUTION Do not use a relative humidity sensor and CO
2
 sensor on the same zone controller. 
 
 
 
Sensor specifications 
 
Operating temperature  40° to 130°F (-4° to 54°C) 
Humidity  0 to 99%, non-condensing 
Sensor tolerance  Accuracy at 25°C:  ±2% RH from 10–80% 
±3% RH from 80–99% 
Power  18-36 Vdc  
24 Vac half-wave rectified   
Output 
 
#OPNSENSRH-01:  4-20 mA, 0-5 Vdc, and 0–10 Vdc 
#33ZCSENSRH-01, #33ZCSENDRH-01, 
and #33ZCSENORH-01: 
4-20 mA and 0–10 Vdc 
Physical  Includes a 499 Ohm 1 Watt resistor for conversions of the 4–20 mA signal to 
a +2–10 Vdc output signal 
 
 
 
Wiring specifications 
 
Cable from sensor to controller:  If <100 ft (30.5 meters)        22 AWG, unshielded 
If >100 ft (30.5 meters)        22 AWG, shielded 
Maximum length:  500 feet (152 meters)