Duct Air Temperature sensor
20 Carrier Sensors
Part #33ZCSENDAT
The Duct Air Temperature (DAT) sensor monitors supply air and is required for cooling and heating air source
applications on non-Carrier dampers and for stand-alone operation.
DAT sensor specifications
Operating range -40° to 245°F (-40° to 118°C) with a nominal resistance of 10,000 ohms at
77°F (25°C). See table below.
Sensor tolerance Accuracy of ±0.36°F (0.2°C) from 0° to 70°C
Physical Small, epoxy sensor, 1.25 inch (3.2 cm) long. Includes a mounting grommet and
75-inch cable.
Duct Air Temperature sensor