Relative Humidity sensors
48 Carrier Sensors
Allows calibration of the sensor through imbedded calibration
software. Toggle the #1 switch from Off to On to Off again for a
decrease of 0.5% RH.
To correct a 1% drift, perform the above toggle sequence
twice.
This is a single point calibration and is not recommended for
critical applications. Contact the factory before doing any field
calibration.
Reset to
Original
Calibration
Resets the transmitter to its original factory calibration. Turn switch
#1 and #2 On for a minimum of 5 seconds and then off again.
RH conversion formulas
Use the following table to convert transmitter output signal to %RH.
EXAMPLE:
If signal output is...
4 mA = 0% RH
20 mA = 100% RH
12 mA (12mA-4mA)/0.16 = 50% RH
0 Vdc = 0% RH
10 Vdc = 100% RH
8 Vdc 8 Vdc/0.10 = 80%RH
(#OPNSENSRH-01 only)
0 Vdc = 0% RH
5 Vdc = 100% RH
2 Vdc 2 Vdc/0.05 = 40% RH