SPT sensors
4 Carrier Sensors
Sensor
Features
SPT Pro
Part #SPP
LCD display
MANUAL ON button to override schedule
WARMER and COOLER buttons to adjust
setpoint
INFO button to cycle through zone and
outside air temperatures, setpoints, and
local override time
Local access port
SPT Pro Plus
Part #SPPF
(Used with Water Source Heat Pump only)
LCD display
MANUAL ON button to override schedule
WARMER and COOLER buttons to adjust
setpoint
INFO button to cycle through zone and
outside air temperatures, setpoints, and
local override time, plus 4 additional inputs
that can be defined in EIKON LogicBuilder
MODE button to cycle through custom
programmed modes
FAN SPEED button to adjust fan speed
Local access port
SPT sensor specifications
Sensor tolerance Precision Thermistor. Standard accuracy ±0.45°F (0.25°C). Less than
±0.18°F (0.1°C) drift over a 10 year period.
Power Supplied by the 4-conductor cable (+12 Vdc @ 250 mA) from the controller.
Communication 115 kbps
Local access port For local access to start up and troubleshoot system
Environmental operating
range
32–122°F (050°C), 1090% relative humidity, non-condensing
Mounting Standard 4x2-in. electrical box using provided 6-32 by 1/2 in. mounting
screws.