Installing the Zone Ctrl II
Zone Ctrl II and
VAV Zone II Secondary Duct Installation and Start-up Guide CARRIER CORPORATION ©2019
Error! No text of specified style in document.
27 All rights reserved
VAV Zone II Secondary Duct
The LED's on the VAV Zone II Secondary Duct show the status of certain functions.
If this LED...
Is...
Status is...
Pwr
On The VAV Zone II Secondary Duct has power
RX
On The VAV Zone II Secondary Duct is receiving data from the network segment
TX
On The VAV Zone II Secondary Duct is transmitting data over the network
segment
CW
On The actuator motor is turning clockwise
CCW
On The actuator motor is turning counterclockwise
Run
Flashing VAV Zone II Secondary Duct is operating