Module AC Input Alarms
Text ID Name Level Def. Map Check and Action
172 THD Too High Minor Check AC IN configuration and live value
173
Output
Synchronization
Minor Check AC IN configuration and live value
174 Error (174) Minor
175
Output
Synchronization
Minor Check synchronization between AC IN and AC OUT
176 Inv. Synchronization Minor Check synchronization between AC IN and AC OUT
177
Synchronization
failure
Minor Check synchronization between AC IN and AC OUT
179
Source V Too Low
Stop
Minor Check AC IN configuration and live value
180
Source V Too High
Stop
Minor Check AC IN configuration and live value
181
Source Frequ. Too
Low
Minor Check AC IN configuration and live value
182
Source Frequ. Too
High
Minor Check AC IN configuration and live value
183 Phase Not Ready Minor Check AC IN configuration and live value
184 Backfeed Error Minor Inverter in backfeed protection
188 Error (188) Minor
189 Error (189) Minor
190 Error (190) Minor
191 Error (191) Minor
Module DC Input Alarms
Text ID Name Level Def. Map Check and Action
193 Ok No error on DC IN
194
Source V Too Low
Transfert
Minor Check VDC parameter and live value
195
Source V Too High
Transfert
Minor Check VDC parameter and live value
196 Error (196) Minor
202
Source V Too Low
Transfert
Minor Check VDC parameter and live value
203
Source V Too High
Transfert
Minor Check VDC parameter and live value
204
Source V Too Low
Stop
Minor Check VDC parameter and live value
75 – Monitoring T2S - ETH User Manual – v1.4
Annex 2: Module alarms - T2S ETH