33
Instruction Manual
CVM-C4
 6.1.- CONFIGURATION OF THE INPUT
Figure 16 showstheinputcongurationmenufromwhichthemeasurementsystemandthe
primaryandsecondarycurrentandvoltagearecongured.
Measurement system
Primary voltage
Secondary voltage
Primary current
Secondary current
Save conguration
inpt
 nEt
 n34
.
inpt
pt 1
0380
.
.
V
k
inpt
pt 2
0380
.
.
V
inpt
Ct 1
0005
.
.
A
k
inpt
Ct 2
0005
.
A
SAuE
>3s
>3s
>3s
>3s
>3s
>3s
inpt
 nEt
 n34
.
inpt
pt 1
0380
.
.
V
inpt
pt 2
0380
.
.
V
inpt
Ct 1
0005
.
.
A
k
inpt
Ct 2
0005
.
A
SAuE
  no
Figure 16: Input conguration menu
6�1�1�- MEASUREMENT SYSTEM
Inthisscreenwecancongurethemeasurementsystemusedintheinstallation.
inpt
 nEt
 n34
.
>3s
inpt
 nEt
 n34
.
With a long keystroke (>3s), press  toaccessthevalue'sconguration.
Use the keys   and   to browse through the different options:
 n34, three-phase network measuring with 4-wire connection.
  n.33, three-phase network measuring with 3-wire connection.
  n.12, single-phase measuring.