Use the keys   and   to browse through the menu screens.
6�1�4�- PRIMARY CURRENT
Thisscreenisusedtocongurethevalueoftheprimarycurrent.
inpt
Ct 1
0005
.
.
A
k
>3s
inpt
Ct 1
0005
.
.
A
k
With a long keystroke (>3s), press  toaccessthevalue'sconguration.
Use the key  tomodifythevalueoftheashingdigit.
When the desired value is shown on the screen, press the   and   keys to skip the digit.
When you reach the last digit and press the   key, you select the position of the decimal 
point. Use the key   to modify the decimal point.
Minimum conguration value: 0.001 kA
Maximum conguration value: 20 kA
With a long keystroke, press   to validate the data.
Use the keys   and   to browse through the menu screens.
6�1�5�- SECONDARY CURRENT
Thisscreenisusedtocongurethevalueofthesecondarycurrent.
inpt
Ct 2
0005
.
A
>3s
inpt
Ct 2
0005
.
A
With a long keystroke (>3s), press  toaccessthevalue'sconguration.
Use the key  tomodifythevalueoftheashingdigit.
When the desired value is shown on the screen, press the   and   keys to skip the digit.
Minimum conguration value: 1 A
Maximum conguration value: 6 A
With a long keystroke, press   to validate the data.
Use the keys   and   to browse through the menu screens.