4�7�2� PROTOCOL
IntheModbusprotocol,theCVM-C5unitusestheRTU(RemoteTerminalUnit)mode�
TheModbusfunctionsimplementedintheunitareasfollows:
Function 03 and 04� ReadingnWords(2bytes)�Functionusedforreadingtheparameters
beingmeasuredbytheCVM-C5�Allparametersare32-bitslong,whichiswhytoaskeach
parametertakestwoWords�
Function 10�Writingmultiplelogs�
4.7.2.1. Selecting the active tari
TheCVM-C5hastwotaris,T1andT2,selectableusingthefollowingModbusfunction:
Selecting the active tariff:
Address Function
Registro
inicial
No registers No bytes Tari CRC
NP
(1)
10 1388 0001 02 000T
(2)
xxxx
(1)
NP: Peripheralnumber
(2)
Theselectionoftheactivetariisselectedaccordingtothefollowingtable:
Table 16:Selecting tari.
Code Tari
0 TariT1
1 TariT2
Response:
Address Function
Initial
register
No registers CRC
NP
(1)
10 1388 0001 xxxx
reading active tari:
Address Function
Initial
register
No registers CRC
NP
(1)
04 1388 0001 xxxx
Response:
Address Function No bytes No registers CRC
NP
(1)
04 02 000T
(2)
xxxx