Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-06
Chapter 9      Replacement Procedures
Replacing the Front Door and Air Intake Assemblies on the Cisco Nexus 7018 Chassis
Figure 9-41 Attaching the Left Door Stopper
Step 3
Position the right door stopper (has an R on its base) on the middle of the right side of the cable 
management frame and fasten it with two M3x14 pan-head screws as shown in Figure 9-42. Tighten 
these two screws to 8.4 to 11 in-lb (0.9 to 1.2 N·m).
1 Left door stopper identified with an L on 
the bottom of the base.
3 Screw holes on the cable management assembly.
2 Two M3x14 screws that fasten the stopper 
to the left side of the cable management 
assembly.