Power Supply Cable Specifications
Power Supply Cable Specifications
For specifications of the AC power cables that you can connect to a 6-kW AC power supply unit, see
Table A-12. For specifications of the AC power cord connectors attached to the 7.5-kW power supply
units, see Table A-13 on page A-13. For the specification of the DC power cord that you connect to the
6-kW power supply unit, see Table A-14 on page A-14.
Table A-11 Power Availability for 6.0-kW DC Power Supply Units
Power Inputs
Combined
Mode
Power
Supply
Redundancy
Mode
Input Source
Redundancy
Mode
Full
Redundancy
Mode
Dual inputs per power supply unit
1 power supply unit
2 power supply unit
3 power supply unit
4 power supply unit
6,000 W
12,000 W
18,000 W
24,000 W
—
6,000 W
12,000 W
18,000 W
3,000 W
6,000 W
9,000 W
12,000 W
—
6,000 W
9,000 W
12,000 W
Single input per power supply unit
1 power supply unit
2 power supply unit
3 power supply unit
4 power supply unit
3,000 W
6,000 W
9,000 W
12,000 W
—
3,000 W
6,000 W
9,000 W
—
—
—
—
—
—
—
—
Table A-12 6-kW AC Power Supply Power Cords
Locale Power Cord Part Number Cord Set Rating
Power Cord Reference
Illustration
Australia and New Zealand CAB-AC-16A-AUS 16A, 250 VAC Figure A-1
Peoples Republic of China CAB-AC-16A-CH 16A, 250 VAC Figure A-2
Continental Europe CAB-AC-2500W-EU 16A, 250 VAC Figure A-3
International CAB-AC-2500W-INT 16A, 250 VAC Figure A-4
Israel CAB-AC-2500W-ISRL 16A, 250 VAC Figure A-5
Japan and North America
(non locking) 200-240 VAC
operation
CAB-AC-2500W-US1 16A, 250 VAC Figure A-6
Japan and North America
(locking) 200-240 VAC
operation
CAB-AC-C6K-TWLK 16A, 250 VAC Figure A-7
Japan and North America
100-120 VAC operation
CAB-7513AC 16A, 250 VAC Figure A-8
Power distribution unit (PDU) CAB-C19-CBN 16A, 250 VAC Figure A-9