Advanced M52 Microprocessor User's Guide
ADVANCED M52UMCT2019 COLOR 43
Temperature and Humidity Sensor
A
ddress Jumpers
LED Power
As shown above,S01havejumpersandrepresentstheaddressplus8.S02youcanseethetable.
No
S02-1
S02-2
S02-3
485
1
0
0
0
1
2
1
0
0
2
3
0
1
0
3
4
1
1
0
4
5
0
0
1
5
6
1
0
1
6
7
0
1
1
7
8
1
1
1
8
ThereturnsensorRS485addressis11(8+3:S01onS02‐2on),thesupplysensoris12(8+4:S01onS02‐1on,
S02‐2on)
Now we only use RS485 Address 11&12
RS485 Address 11 is the return Air Sensor.
RS485 Address 12 is the supply Air Sensor.
Alternate Temperature & Humidity Sensor