ID-FLX Lite Global Guide
119
Setpoint group Engine parameters Related FW 2.5.0
Range [units] IDLE, NOMINAL [-]
Default value -
Step -
Comm object 10046 Related applications
Description
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.
IDLE Cooling is executed at Idle speed.
NOMINAL Cooling is executed at Nominal speed. Default state.
Note: Binary output IDLE/NOMINAL must be configured and connected to speed governor. Engine Idle
speed must be adjusted on speed governor.
Cooling speed
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 30 -
Step 1
Comm object 8258 Related applications
Description
Run time of the unloaded engine to cool the engine before stop.
Cooling time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 180 -
Step 1
Comm object 8662 Related applications
Description
Run time of engine after cooling pump. COOLING PUMP (PAGE 202) is closed when the engine starts and
opens AfterCool time delayed after engine stops.
AfterCool time
6 back to List of setpoints