ID-FLX Lite Global Guide
118
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 12 -
Step 1
Comm object 9097 Related applications
Description
Idle time delay starts when RPM exceeds Starting RPM (page 114). Start fail is detected when during Idle
state RPM decreases below 2.
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes. IDLE/NOMINAL (PAGE 202) opens during Cooling period again.
Note: Engine can be switched between Idle and Running state by NOMINAL/IDLE (PAGE 192) in MAN
mode.
Idle time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] Starting RPM (page 114) .. MinSpeedLim (page 124) [RPM]
Default value 800 -
Step 1
Comm object 9946 Related applications
Description
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by
NOMINAL/IDLE (PAGE 192) and after Engine ShutDown.
Idle speed
6 back to List of setpoints