Setpoint group Engine parameters Related FW 2.5.0
Range [units] Starting RPM (page 114) .. MaxSpeedLim (page 124) [RPM]
Default value 1200 -
Step 1
Comm object 10096 Related applications
Description
The setpoint presets the minimum engine speed in the “Running” operation state. Also see other conditions
in the chapter below.
Note: See Speed request chart (page 64).
MinSpeedLim
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] MinSpeedLim (page 124) .. 4000 [RPM]
Default value 2700 -
Step 1
Comm object 10097 Related applications
Description
The setpoint presets the maximum engine speed in the “Running” operation state. Also see other conditions
in the chapter below.
Note: See Speed request chart (page 64).
MaxSpeedLim
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] MinSpeedLim (page 124) .. MaxSpeedLim (page 124) [RPM]
Default value 1250 -
Step 1
Comm object 10099 Related applications
Description
The setpoint presets the required engine speed during the ‘Speed Sel 1’ binary input is active. Function
depends on RetToSpeedAdj setting.
Note: See Speed request chart (page 64).
BI Speed Sel 1