Setpoint group Engine parameters Related FW 2.5.0
Range [units] MinSpeedLim (page 124) .. MaxSpeedLim (page 124) [RPM]
Default value 1300 -
Step 1
Comm object 10523 Related applications
Description
The setpoint presets the required engine speed during the ‘Speed Sel 2’ binary input is active. Function
depends on RetToSpeedAdj (page 123) setting.
Note: See Speed request chart (page 64).
BI Speed Sel 2
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] MinSpeedLim (page 124) .. MaxSpeedLim (page 124) [RPM]
Default value 1450 -
Step 1
Comm object 10524 Related applications
Description
The setpoint presets the required engine speed during the ‘Speed Sel 3’ binary input is active. Function
depends on RetToSpeedAdj (page 123) setting.
Note: When none of the binary inputs: ‘Speed Sel1’, ‘Speed Sel2’ and ‘Speed Sel3’, ‘Speed Up’ and
‘Speed Down’ has not been configured then engine speed is given by the ECU SpeedAdj (page 123)
setpoint.
Note: See Speed request chart (page 64).
BI Speed Sel 3
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 1 .. MaxSpeedLim (page 124) [RPM/s]
Default value 50 -
Step 1
Speed Ramp