ID-FLX Lite Global Guide
123
Setpoint group Engine parameters Related FW 2.5.0
Range [units] MinSpeedLim (page 124) .. MaxSpeedLim (page 124) [RPM]
Default value 1500 -
Step 1
Comm object 13095 Related applications
Description
Enables to adjust engine speed in ECU via CAN bus. Speed request value after the Idle time is over and no
other speed selection is activated.
Speed request in % range is calculated using the setpoints 0%ofSpeedReq (page 127) and
100%ofSpeedReq (page 127).
Note: See Speed request chart (page 64).
ECU SpeedAdj
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] DISABLED, ENABLED [-]
Default value -
Step -
Comm object 11838 Related applications
Description
Selection among SPEED SEL1 (PAGE 193), SPEED SEL2 (PAGE 193), SPEED SEL3 (PAGE 193) behavior.
DISABLED
Speed request is set by LBI Speed Sel1, 2, 3 (see appropriate setpoints) by rising
edge (button, no switch) - i.e. Speed request stay constant after the input is opened
and can be changed by SPEED UP (PAGE 192) and SPEED DOWN (PAGE 192).
Default state.
ENABLED
Speed request goes to ECU SpeedAdj when the LBI Speed Sel1, 2, 3 are opened.
Speed request can be changed by SPEED UP (PAGE 192) and SPEED DOWN (PAGE
192) when LBI Speed Sel1, 2, 3 are closed.
Note: See Speed request chart (page 64).
RetToSpeedAdj
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 30 -
Step 1
Comm object 10612 Related applications N/A
Description
This setpoint is used to set duration of time for which LBO ReliefValActiv will be activated.
ReliefVal time
6 back to List of setpoints