ID-FLX Lite Global Guide
193
Related FW 2.5.0 Related applications
Comm object 710
Description
If the input is active, the Speed request = BI Speed Sel 1 (page 124). The function is affected by
RetToSpeedAdj (page 123).
Note: See Speed request chart (page 64).
Speed Sel1
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 711
Description
If the input is active, the BI Speed Sel 2 (page 125) may give the engine speed value for Speed request to
an ECU engine. The Speed Request value may also depend on the conditions which are described in the
chapter below.
Note: See Speed request chart (page 64).
Speed Sel2
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 712
Description
If the input is active, the BI Speed Sel 3 (page 125) may give the engine speed value for Speed request to
an ECU engine. The Speed Request value may also depend on the conditions which are described in the
chapter below.
Note: RetToSpeedAdj (page 123) = DISABLED, Speed request is adjusted by BI Speed Sel1, 2, 3
edge (button press), i.e. input can be opened and Speed request stay constant.
Note: RetToSpeedAdj (page 123) = ENABLED, Speed request is adjusted by BI Speed Sel1, 2, 3 level
(switch), i.e. when input is opened Speed request go back to ECU SpeedAdj (page 123) level.
Note: SpeedSel1, 2,.3 binary inputs are active only when LAI SpdRequest (page 129) = OFF.
Note: When more binary inputs are active at the same time, e.g. all binary inputs: ‘Speed Sel1’, ‘Speed
Sel2’, ‘Speed Sel3’ then requested speed is given by BI Speed Sel 1 (page 124) (lowest index)
setpoint.
Note: See Speed request chart (page 64).
Speed Sel3
6 back to List of LBI