ID-FLX Lite Global Guide
194
Related FW 2.5.0 Related applications
Comm object 107
Description
Switch display texts between two languages.
Lang selection
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 312
Description
Initial condition: Running engine.
Rising edge CONVEYOR (PAGE 194) activates HORN (PAGE 203) for Conveyor horn (page 127). And after
horn is over activates the BO Conveyor.
The second rising edge of CONVEYOR (PAGE 194) opens the BO Conveyor. BO Conveyor is deactivated in
case of Sd protection.
Conveyor
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 313
Description
Active input switches the Load limit request to Load request 2 (page 136) setpoint.
LoadRequest2
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 314
Description
Active input disables the Load limit PI loop and switches analog output to constant Load Bias (page 135).
LoadRegDisable
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 315
Description
Active input switches the Regulator limit request to Request 2 (page 131) setpoint.
RegRequest2